Advanced commissioning
6.5 Drive control via PROFINET
6.5.6

NAMUR message word

Fault word according to the VIK-NAMUR definition (MELD_NAMUR)
Bit Significance
0
1
2
3
4
5
6
7
8
10 1 = fault in the internal converter communication
11 1 = line fault
15 1 = other fault
6.5.7

Parameter channel

Structure of the parameter channel
The parameter channel consists of four words. The 1st and 2nd words transfer the parameter
number, index and the type of task (read or write). The 3rd and 4th words contain the
parameter content. The parameter contents can be 16-bit values (such as baud rate) or 32-bit
values (e.g. CO parameters).
Bit 11 in the 1st word is reserved and is always assigned 0.
You can find application examples relating to the parameter channel at the end of this
section.
AK: Request and response IDs
Bits 12 ... 15 of the 1st parameter channel word contain the request and response identifier
AK.
120
1 = converter signals a fault
1 = line fault: phase failure or inadmissible voltage
1 = DC link overvoltage
1 = power unit fault, e.g. overcurrent or overtemperature
1 = converter overtemperature
1 = ground fault/phase fault in the motor cable or in the motor
1 = motor overload
1 = communication error to the higher-level control system
1 = fault in a safety-relevant monitoring channel
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
P no.
p2051[5] = r3113
SINAMICS G115D distributed drive