Condensation Drain Hole (Optional); Connecting The Motor In The Terminal Box; General Notes For Motor Connection (Wall Mounted) - Siemens SINAMICS G115D Operating Instructions Manual

Distributed drive
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Additional information on the SIMOGEAR geared motor
11.2 Specific data motor
11.2.9

Condensation drain hole (optional)

When installing the surface-cooled motor, take care that the condensation drain holes are at
the lowest point.
11.2.10

Connecting the motor in the terminal box

For the Motor Mounted version, the converter is permanently connected to the motor. For
the connection of the converter to the electricity supply network, see previous chapters.
11.2.10.1

General notes for motor connection (Wall Mounted)

Unintentional starting of the drive unit
Any work must be performed with the machine stationary, isolated from the power supply
and locked-out so that it cannot be switched back on again. This also applies to auxiliary
circuits, e.g. PT 1000.
Check that the unit is in a no-voltage condition.
Deviations in the voltage, frequency, waveform and/or symmetry of the line supply increase
the temperature rise.
This also negatively impacts the electromagnetic compatibility.
Before starting work, make sure that a protective conductor is securely connected.
Note
Pre-assembled conductors may only be used with fixed routed at temperatures below -30 °C.
Alternating bends are not allowed at these temperatures.
Connect the motor in such a way that a permanently safe electrical connection is ensured.
Wire ends must not protrude. Use matching cable end pieces.
Connect the line voltage in the terminal box. Arrange the terminal link according to the
circuit diagram for star or delta connection in the terminal box.
If the motor has been ordered with a dispatch circuit, the terminal links are already
connected to the terminal board as star or delta connection.
Select the connection cables according to DIN VDE 0100. Take into account the rated current
and the plant-specific conditions.
The following required information for connection is specified in the technical data:
• Direction of rotation
• Number and arrangement of the connections
• Circuit / connection of the motor winding.