Advanced commissioning
6.15 Setpoint processing
6.15.3

Inhibit direction of rotation

Function description
In the factory setting of the converter, both motor directions of rotation are enabled.
Set the corresponding parameter to a value = 1 to permanently block directions of rotation.
Example
Table 6- 26
Parameter
p1110[0] = 1
p1110[0] = 722.3
Parameters
Parameter
p1110[0...n]
p1111[0...n]
212
Application examples showing how a setpoint is inverted
Description
Negative direction of rotation is permanently inhibited.
Digital input 3 = 0: Negative direction of rotation is enabled.
Digital input 3 = 1: Negative direction of rotation is inhibited.
Description
BI: Inhibit negative direction
BI: Inhibit positive direction
Setting
Sets the signal source to disable the negative
direction.
Factory setting: 0
Sets the signal source to disable the positive di-
rection.
Factory setting: 0
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
SINAMICS G115D distributed drive