Parameters
Parameters of the fault buffer and the fault history
Parameter
r0945[0 ... 63]
r0948[0 ... 63]
r0949[0 ... 63]
p0952
r2109[0 ... 63]
r2130[0 ... 63]
r2131
r2133[0 ... 63]
r2136[0 ... 63]
Extended settings for faults
Parameter
You can change up to 20 different faults into alarms, suppress faults, modify the fault response, or
modify the acknowledgement mode:
p2100[0 ... 19]
p2101[0 ... 19]
p2118[0 ... 19]
p2119[0 ... 19]
SINAMICS G115D distributed drive
Operating Instructions, 09/2020, FW V4.7 SP13, A5E48681219B
Description
Fault code
Fault time received in milli-
seconds
Fault value
Fault cases counter
Fault time removed in milli-
seconds
Fault time received in days
Actual fault code
Fault value for float values
Fault time removed in days
Description
Changing fault response,
fault number
Changing the fault reaction,
reaction
Changing message type,
message number
Changing message type,
type
Alarms, faults and system messages
8.5 Faults, fault buffer and fault history
Setting
Displays the numbers of the faults that have oc-
curred.
Displays the system runtime in milliseconds when
the fault occurred.
Displays additional information about the fault
that occurred (as integer number).
Number of fault cases that have occurred since
the last acknowledgement.
With p0952 = 0, you delete the fault buffer and
the fault history.
Factory setting: 0
Displays the system runtime in milliseconds when
the fault was removed.
Displays the system runtime in days when the
fault occurred.
Displays the code of the oldest active fault.
Displays additional information about the fault
that occurred for float values.
Displays the system runtime in days when the
fault was removed.
Setting
Selects the faults for which the fault response
should be changed.
Factory setting: 0
Sets the fault reaction for the selected fault.
0: NONE
1: OFF1
2: OFF2
3: OFF3
5: STOP2
6: Internal armature short-circuit / DC braking
Factory setting: 0
Selects faults or alarms for which the message
type should be changed.
Factory setting: 0
Sets the message type for the selected fault or
alarm.
1: Fault
2: Alarm
3: No message
Factory setting: 1
307