Commissioning
2.2 STARTER commissioning tool
Parameterizing the interface in the expert list
1. Assign the "Name of Station" using parameter p8900
2. Assign the "IP Address of Station" using parameter p8901 (factory setting 169.254.11.22)
3. Assign the "Default Gateway of Station" using parameter p8902 (factory setting 0.0.0.0)
4. Assign the "Subnet Mask of Station" using parameter p8903 (factory setting 255.255.0.0)
5. Activate the configuration with p8905 = 1
6. Activate the configuration and save with p8905 = 2
2.2.5

Activating online operation: STARTER via PROFINET IO

Online operation with PROFINET IO is implemented using TCP/IP.
Preconditions
● STARTER from version 4.1.5 or higher
● Control Unit CU320-2 PN
● Communication Board CBE 20 in the Control Unit
STARTER via PROFINET IO (example)
Figure 2-10
74
Connecting the programming device to the target device via PROFINET (example)
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3