Tests
3.2 Function test
3.2.3

Inputs and outputs of the TM modules in the control cabinet

Fundamentals
The inputs and outputs of the TM modules extend the digital and possibly analog inputs and
outputs of the Control Unit. The switching logic of the inputs and outputs between the TM
module and the Control Unit are checked.
Test procedure
1. Signals are applied to the inputs of the TM modules and read out at the Control Unit.
2. Signals are defined at the Control Unit and read out at the outputs of the TM modules.
Result
The test is passed if the switching logic matches the information in the circuit diagram.
3.2.4

Auxiliary voltages

Fundamentals
Tests are performed according to DIN EN 60146-1. The auxiliary voltages are visually checked
using indicator lights or using a voltmeter.
Test procedure
1. The drive power section is switched off.
2. The auxiliary voltages are switched on.
3. The auxiliary voltages are checked.
Result
The test is passed if all of the auxiliary voltages are available.
3.2.5

Message "Ground fault monitoring"

Fundamentals
The test reveals whether a message is displayed on the test station computer when a ground
fault occurs.
Test procedure
1. The auxiliary voltage is present.
2. The signal cable for signaling the ground fault is interrupted.
24
SINAMICS SL150 6SL3865 F03 F70 F98 F79 F76
Reference Manual Rev.201902141427 SL150 wassergekühlt