Factory settings (defaults) of customer interface on SINAMICS G130

The following factory settings are provided to simplify configuring of the customer interface and commissioning. The
interfaces can also be assigned as required at any time.
1.
The converter is controlled via the PROFIBUS interface which is integrated as standard. The digital inputs and
outputs on the Control Unit are used to incorporate external alarm and/or error messages and control signals.
Terminal block on CU320
-X122
Factory setting
DI0
Not assigned
DI1
Not assigned
DI2
Not assigned
DI3
Acknowledge fault
M1
M1
DI/DO8
Inverter enable (Run)
DI/DO9
No fault
M (GND)
DI/DO10
P24
DI/DO11
External alarm
M (GND)
-X132
DI4
OFF 2
DI5
OFF 3
DI6
External fault
DI7
Not assigned
M (GND)
DI/DO12
Error message acknowledgement, Braking
Module
DI/DO13
P24
M (GND)
DI/DO14
P24
DI/DO15
P24
M (GND)
The factory settings of the bidirectional inputs/outputs are underscored.
1)
A jumper should be inserted here if these inputs are not used.
SINAMICS Engineering Manual – May 2008
174/396
© Siemens AG
1)
1)
1)
1)
Comment
Factory-set as output
Low active
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module
Output is used (factory-set) in conjunction with the Braking
Module
Factory-set as output
Factory-set as output
Factory-set as output