Has02.1-006 With Motor Cable And Mains Filter - Bosch Rexroth IndraDrive HMV Project Planning Manual

Supply units and power sections
Table of Contents

Advertisement

356/369
Bosch Rexroth AG | Electric Drives
Accessories

HAS02.1-006 With Motor Cable and Mains Filter

and Controls
Using the shielding plate guarantees optimum shield contact of the
motor cable. You should therefore, where possible, always use the
shielding plate.
The shielding plate is only available as an option.
1
fixing device
2
shielding plate
3
clip
Fig.11-52:
HAS02.1-006 at bottom of mains filter (rated current 50 A)
1. Hang up fixing device at bottom of mains filter at threaded bolts and fasten
with supplied nuts.
2. Screw shielding plate to fixing device.
3. Fix shield of cable to shielding plate with appropriate clip.
The shield terminals must not be used to provide strain relief.