Bosch Rexroth IndraDrive HMV Project Planning Manual page 203

Supply units and power sections
Table of Contents

Advertisement

Project Planning Manual | Rexroth IndraDrive
Description
mains fuse according to IEC
60364‑5‑52; at nom. data with
mains choke; U
LN_nenn
required wire size according to
IEC 60364‑5‑52; at I
11)
L_cont
required wire size according to
UL 508 A (internal wiring); at I
(UL)
12)
Symbol
Unit
A
A
mm
2
LN
A
AWG
L_cont
LN
1)
600 V AC or less, use listed AC input line fuses or listed circuit breakers
2) 3)
mains voltage > ULN: use a transformer with grounded neutral point,
don't use autotransformers!
4)
otherwise use mains choke HNL
5)
HMV0x.xR: Rsc=100; HMV0x.xE, HCS0x.xE: Rsc=50
6)
depending on mains input voltage ULN; HMV01.1R see following note;
HMV: constant current charge, HCS: resistance charge; minimum of
250.000 load cycles
7)
without external capacities on DC bus
8) 9)
find interim values by interpolation
10)
at PDC_cont
11)
copper wire; PVC-insulation (conductor temperature 70 °C); installation
method B2; Table B52-4; Ta ≤ 40 °C
12)
copper wire; PVC-insulation (conductor temperature 90 °C); Table
13.5.1; Ta ≤ 40 °C
Fig.7-15:
HMV - Data for mains voltage supply
Qualitative characteristic TPF vs. DC bus power PDC_cont
1
with mains choke
2
without mains choke
Fig.7-16:
Qualitative characteristic TPF vs. DC bus power PDC_cont
Electric Drives
and Controls
HMV01.1E-W0030
HMV01.1E-W0075
63
10
AWG 6
AWG 1
| Bosch Rexroth AG
193/369
IndraDrive M Supply Units
HMV01.1E-W0120
160
250
50
95
AWG 4/0

Hide quick links: