Bosch FPP-RNAC-8A-4C Operation And Installation Manual

Bosch FPP-RNAC-8A-4C Operation And Installation Manual

Remote nac power supply
Table of Contents

Advertisement

FPP-RNAC-8A-4C
Operation and Installation Guide
Remote NAC Power
EN
Supply

Advertisement

Table of Contents
loading

Summary of Contents for Bosch FPP-RNAC-8A-4C

  • Page 1 FPP-RNAC-8A-4C Operation and Installation Guide Remote NAC Power Supply...
  • Page 2 FPP-RNAC-8A-4C | Operation and Installation Guide | Notice to Users, Installers, Authorities Having Jurisdiction, and other involved parties: This product incorporates field- programmable software. In order for the product to comply with the requirements in the Standard for Control Units and...
  • Page 3: Table Of Contents

    FPP-RNAC-8A-4C | Operation and Installation Guide | Figures Contents Figure 1: FPP-RNAC-8A-4C Remote NAC Power Supply Board........5 Overview ............4 Figure 2: FPP-RNAC-8A-4C Enclosure and Module Control...........4 Board Installation ........7 1.1.1 Option Bus Control ...........4 Figure 3: AC Power Connections......9 1.1.2...
  • Page 4: 1.0 Overview

    FPP-RNAC-8A-4C | Operation and Installation Guide | 1.0 Overview All outputs are synchronized if the 1.0 Overview conventional inputs are activating the FPP-RNAC-8A-4C. The FPP-RNAC-8A-4C is a Remote Notification Appliance Circuit (NAC) Power Supply designed to add four additional NACs (NFPA 72 Class B, Style Y...
  • Page 5: Expander Supervision

    LED lights if the system encounters an error. 2.0 Installing the FPP-RNAC-8A-4C The FPP-RNAC-8A-4C board and the enclosure are shipped together. The board, however, needs to be mounted into the enclosure. Hardware for mounting the board in the enclosure is supplied in the hardware pack.
  • Page 6: Fpp-Rnac-8A-4C Board Installation

    FPP-RNAC-8A-4C | Operation and Installation Guide | 2.0 Installing the FPP-RNAC-8A-4C FPP-RNAC-8A-4C Board Installation The FPP-RNAC-8A-4C board is static- sensitive. Touch ground before handling the board. Doing so discharges any static electricity in your body. 1. Connect the ground wire.
  • Page 7: Fpp-Rnac-8A-4C Enclosure And Board Installation

    FPP-RNAC-8A-4C | Operation and Installation Guide | 2.0 Installing the FPP-RNAC-8A-4C Figure 2: FPP-RNAC-8A-4C Enclosure and Board Installation OPTION BUS 4998149856 GROUND FAULT BOSCH OPEN = DISABLE CLOSE = ENABLE TROUBLE RESET FLASH PROGRAMMING PORT INPUT ACTIVE AC OK SYSTEM TROUBLE...
  • Page 8: 3.0 Wiring The Fpp-Rnac-8A-4C

    FPP-RNAC-8A-4C | Operation and Installation Guide | 3.0 Wiring the FPP-RNAC-8A-4C 3.0 Wiring the FPP-RNAC-8A-4C All terminals are fully protected against electrostatic discharge (ESD) and transients. Use wire gauge based on Table 1 and Table 2. The terminals can accommodate up to 12 AWG (2.0 mm) wire.
  • Page 9: Ac Power Connections

    FPP-RNAC-8A-4C | Operation and Installation Guide | Figure 3: AC Power Connections Figure 4: Install Ferrite Core AC input select switch Ferrite core AC power terminal Ground Neutral Line (120 VAC or 240 VAC) Ferrite core Install the Line and Neutral power connections through the ferrite core as shown in Figure 4.
  • Page 10: Battery Connections (24 Vdc Only)

    Battery Connections (24 VDC Only) The backup battery plugs into the terminals marked BATTERY+ and BATTERY- at the lower center of the board (refer to Figure 5). The FPP-RNAC-8A-4C requires two backup batteries in series. Figure 5: Battery Connections Inside FPP-RNAC-8A-4C Enclosure...
  • Page 11: Battery Connections Using An External Battery Case

    FPP-RNAC-8A-4C | Operation and Installation Guide | Figure 6: Battery Connections Using an External Battery Case O P T I O N B U S 4998149856 G R O U N D F A U L T B O SC H...
  • Page 12: Table 3: Standby Time Calculation

    FPP-RNAC-8A-4C | Operation and Installation Guide | You can use the format in Table 3 to calculate the required battery size to support the system. Use Table 4 and Table 5 on page 13 to estimate the required battery size.
  • Page 13: Table 5: Standby Load Battery Capacity (In Ampere-Hours [Ah])

    Battery Case and the control panel must be in conduit and be no more than 20 ft (6.1 m) from the control panel. All power wiring must exit from the left side of the FPP-RNAC-8A-4C enclosure. •...
  • Page 14: Figure 3: Figure

    Y, G, B, and R (refer to Figure 7). Connect either the option bus or the NAC You can use the option bus connection with a Bosch Input terminals on the FPP RNAC 8A-4C Security Systems, Inc. FPA-1000 or FPD-7024 Fire to the FACP.
  • Page 15: Trouble Relay Connections

    A short circuit on this output causes a trouble board to indicate a fault condition. Refer to Figure 9 condition but does not affect the operation of the for wiring details. FPP-RNAC-8A-4C in any way. Refer to Figure 10 for Figure 9: Wiring the Trouble Relay wiring details.
  • Page 16: Auxiliary Circuits

    FPP-RNAC-8A-4C | Operation and Installation Guide | 3.7.2 Auxiliary Circuits Figure 11: Wiring the NAC outputs and EOL The FPP-RNAC-8A-4C can be configured to supply constant auxiliary power through its NAC outputs. Reverse polarity connections of some notification appliances might not be detected by the FPP-RNAC-8A-4C NAC supervision.
  • Page 17: Dip Switch And Option Bus Settings

    ON (PWR) ON (PWR) 1 When operating in NAC mode (Switch S1, position 3, 4, 5, or 6-= OFF), the FPP-RNAC-8A-4C produces the protocol selected for the output. 2 When operating in one of the SYNC protocols, NAC Input 1 controls strobes and Input 2 controls sounders. This protocol allows the sounders to silence while strobes continue to operate.
  • Page 18: Switch S2

    FPP-RNAC-8A-4C | Operation and Installation Guide | 4.0 DIP Switch and Option Bus Settings Switch S2 Use Switch S2 to set the following (refer to Table 8): • NAC output control • AC failure delay time – 0, 1, 3, and 6 hour delay •...
  • Page 19: Conventional (Polarity Reversal) Inputs 1 And 2

    FPP-RNAC-8A-4C | Operation and Installation Guide | 4.0 DIP Switch and Option Bus Settings Conventional (Polarity Reversal) Inputs 1 and 2 Two factors determine how the four NAC outputs respond to input: • Output protocol set on Switch S1 (refer to Table 7 on page 17) •...
  • Page 20: Option Bus Address

    FPP-RNAC-8A-4C | Operation and Installation Guide | 4.0 DIP Switch and Option Bus Settings Option Bus Address To activate a new address, remove the AC and battery power from the FPP-RNAC-8A-4C. Wait 60 sec. Restore the power after it is removed. The new address becomes active after power is restored to the FPP-RNAC-8A-4C.
  • Page 21: 5.0 Fpp-Rnac-8A-4C Local Status Display

    Table 10 for the label, color, and description of each on-board LED. The FPP-RNAC-8A-4C has a TROUBLE RESET momentary switch to clear latched trouble conditions. The TROUBLE1 - 4 LEDs (refer to Figure 13 on page 22) indicate trouble conditions.
  • Page 22: Figure 13: Fpp-Rnac-8A-4C Leds

    FPP-RNAC-8A-4C | Operation and Installation Guide | 5.0 FPP-RNAC-8A-4C Local Status Display Table 10: Local Status Display LED Functions (continued) Label Color Description SYSTEM Yellow Blink Count Description TROUBLE (The Trouble Relay activates or changes state.) (display priority) Any memory fault (RAM, FLASH, watchdog, unexpected interruptions, stack corruption).
  • Page 23: Specifications

    NAC Outputs (x4) (NFPA 72 Class B, Style Y NAC or Class A, Style Z) Standby Voltage 5 VDC EOL Resistor 2.21 kΩ Bosch Security System, Inc. P/N: 25899 or Programmable from 1 kΩ to 20 kΩ Output Voltage 24 VDC Regulated Line Resistance 1.36 Ω...
  • Page 24 FPP-RNAC-8A-4C | Operation and Installation Guide | 6.0 Specifications Table 11: Specifications (continued) Trouble Relay Output Contact Type Form C Contact Rating 1.5 A, 30 VDC resistive load AC Trouble Relay Output Contact Type Form C Contact Rating 1.5 A, 30 VDC resistive load...
  • Page 25 FPP-RNAC-8A-4C | Operation and Installation Guide | 6.0 Specifications Bosch Security Systems, Inc. | 8/09 | F01U025431-02...
  • Page 26 Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, NY 14450-9199 (800) 289-0096 © 2009 Bosch Security Systems, Inc. F01U025431-02...