Project Planning Manual | Rexroth IndraDrive
Connection Diagram
Notes on Installation
8.18

Terminal Block L+, L- (DC Bus Connection)

WARNING
Function, Pin Assignment
A
cable (to source of control voltage supply)
B
contact bars
Fig.8-56:
Connection points and connections of control voltage
Requirements on the connection to the 24V supply:
maximum allowed inductance of 100 µH (2 twisted single strands, 75 m
long)
parallel line routing where possible
The input 0V is connected in conductive form with the housing po‐
tential. It is therefore impossible to use an insulation monitor at
+24V and 0V against housing.
Lethal electric shock caused by live parts with more than 50 V!
Wait at least 30 minutes after switching off power to allow discharging. To
shorten the waiting time until voltage has fallen below 50 V, you can use
a discharging device (see documentation "Rexroth IndraDrive - Drive Sys‐
tem" or, if existing, chapter "Appendix" in this documentation).
Check whether voltage has fallen below 50 V before touching live parts!
The DC bus connection connects
several drive controllers to one another
a drive controller to additional components
HCS02.1E-W0012 drive controllers do not have a DC bus connec‐
tion.
Electric Drives
| Bosch Rexroth AG
and Controls
Functions and Electrical Connection Points
281/369