X3, Mains Connection; Important Notes - Bosch Rexroth IndraDrive HMV02 Operating Instructions Manual

Table of Contents

Advertisement

DOK-INDRV*-HMV02******-IT01-EN-P
Rexroth IndraDrive Supply Units HMV02
5.2.3

X3, Mains Connection

Important Notes

Notes on Installation
WARNING
Exclusively operate the device
with plugged on connectors (even if there haven't been any lines con‐
nected to the connectors) and
with connected equipment grounding conductor!
Dimension the required cross section of the connection cables according to
the determined phase current I
Equipment grounding conductor: Material and cross section
For the equipment grounding conductor, use the same metal (e.g.
copper) as for the outer conductors.
For the connections from the equipment grounding conductor
connection of the device to the equipment grounding conductor
system in the control cabinet, make sure the cross sections of the
lines are sufficient.
Cross sections of the equipment grounding connections:
For HCS03.1E drive controllers, HMV01 and HMV02 supply
units at least 10 mm
cross sections of the outer conductors of the mains supply
feeder
For HCS02.1E drive controllers, at least 4 mm
but not smaller than the cross sections of the outer conduc‐
tors of the mains supply feeder
Additionally, mount the housing of HCS02.1E to a bare met‐
al mounting plate. Connect the mounting plate, too, with at
least the same cross section to the equipment grounding
conductor system in the control cabinet.
For outer conductors with a cross section greater than 16 mm²,
you can reduce the cross section of the equipment grounding
connection according to the table "Equipment Grounding Conduc‐
tor Cross Section".
Cross-sectional area A of outer conduc‐
tors
A ≤ 16 mm²
16 mm² < A ≤ 35 mm²
35 mm² < A
Fig.5-3:
Equipment Grounding Conductor Cross Section
Bosch Rexroth AG
Lethal electric shock by live parts with more
than 50 V!
and the mains fuse.
LN
(AWG 8), but not smaller than the
2
Minimum cross-sectional area A
equipment grounding connection
A / 2
31/71
Instructions for Use
2
(AWG 10),
of
PE
A
16

Advertisement