Channel Settings; Figure 20: Menu Items "Channel 1 - WAGO 750-564 Manual

4ao u/i 4-channel analog output module; voltage/current for wago-i/o-system 750
Table of Contents

Advertisement

66
Commissioning
Table 51: "Common" Menu Item
Parameter
K-Bus timeout
Post-Delay [ms]
*)
Factory setting
7.1.3.2

Channel Settings

Figure 20: Menu Items "Channel 1" ... "Channel 4"
Menu items [Channel 1] to [Channel 4] contain the channel-specific parameters
of the I/O module. The parameter list is identical for all channels. If you change a
value, a pen symbol appears to the left of the parameter in question, and the
[Write] button, which had been grayed out before, is enabled.
Click the [Write] button to save any settings you have been made and apply
them to the I/O module.
Manual
Version 1.0.0
Value
Description
If the I/O module watchdog is triggered
[16-bit decimal
(e.g., in the event of a faulty local bus
value]
connection), the outputs of the individual
channels switch to a defined output state
(see section "Channel Settings"). If the
error is eliminated, the I/O module waits for
the amount of time specified here before a
[Input field]
change to the output channels occurs. This
*)
0...600
...65535
prevents output value jumps when the local
bus restarts.
WAGO-I/O-SYSTEM 750
750-564 4AO U/I

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4ao u/i

Table of Contents