To enable or disable HBX Mode:
1. Access the MATE menu as shown in Figure 113.
2. Use the control wheel to select the High Battery Transfer menu option.
Press the button in the center of the control wheel to select the menu.
3. Use the control wheel to change Enable to Disable.
Press the button in the center of the control wheel to accept the selection.
4. Use the control wheel to increase or decrease the value next to Grid Connect.
Press the button in the center of the control wheel to select the set point.
5. Use the control wheel to increase or decrease the value next to Grid Disconnect.
Press the button in the center of the control wheel to select the set point.
6. Use the control wheel to increase or decrease the value next to Grid Connect SOC.
Press the button in the center of the control wheel to select the set point.
7. Use the control wheel to increase or decrease the value next to Grid Disconnect SOC.
Press the button in the center of the control wheel to select the set point.
128
Figure 126
MATE High Battery Transfer Screen
MATE3 Settings
Set Points:
Enabled/Disabled
Grid Connect xx.x VDC
(inverter dependent)
Delay 0 to 240 minutes
Grid Disconnect xx.x VDC
(inverter dependent)
Delay 0 to 240 minutes
Grid Connect SOC
10% to 100%
Grid Disconnect SOC
50% to 100%
900-0117-01-00 Rev A