Section 9
9.1

Overview

The IED can support synchrophasor data communication via IEEE C37.118 and/or IEEE1344 with
maximum 8 TCP clients and 6 UDP client groups, simultaneously.
The rear OEM ports are used for IEEE C37.118/1344 communication. The same ports can also be
used for substation bus (IEC 61850-8-1) communication and process bus (IEC/UCA 61850-9-2LE)
communication where applicable.
In order to establish a connection between PMU and a TCP/UDP client (PDC client), an Ethernet
communication link (e.g. optical fiber) shall be available and the required parameters on both PMU
and the TCP/UDP client shall be set. For the purpose of this section, an Open PDC tool (PMU
Connection Tester) installed on a PC is used as the TCP/UDP client.
9.2

Setting the PMU station communication (PMU Report)

1.
Check the settings for the PMU Report parameters by navigating to: Main menu/
Configuration/Communication/Station communication/phasor measurement/PMU
Report/PMUREPORT:1
1.1.
1.2.
2.
Check the operation of the required phasor channels (PHASORREPORT) by navigating to:
Main menu/Configuration/Communication/Station communication/phasor
measurement/PMU Report/PHASORREPORT:x.
9.3
Setting the PMU station communication (PMU
configuration)
To enable IEEE C37.118/1344 communication, the corresponding OEM ports must be activated.
The galvanic Ethernet front port and the rear optical ports can be used for IEEE C37.118/1344
communication.
To enable IEEE C37.118/1344 synchrophasor communication:
1.
Enable communication for by navigating to: Main menu/Configuration/Communication/
Ethernet configuration.
Line distance protection REL670
Commissioning manual
Establishing connection and verifying
the IEEE C37.118/1344 communication
Make sure that the operation of at least one PMU instance (e.g. PMU1) is
Enable sending the frequency data by setting the parameter
© Copyright 2017 ABB. All rights reserved

Establishing connection and verifying the IEEE C37.118/1344 communication

Section 9
GUID-EFD77C28-6F7C-4277-8C7E-30E78CC8EFAD v3
GUID-B8DCD7BA-AEBA-4977-89D4-2F18ECE34A2F v1
Enabled .
SendFreqInfo to Enabled .
GUID-B4BA9F74-5E28-42FC-8F33-0BC98D5AE6B0 v2
69