ABB Relion 670 Series Commissioning Manual page 191

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
Vpickup
ANSIEQUATION2427 V1 EN-US
4.
Decrease the voltage slowly and note the reset value.
5.
Set and apply about 20% higher voltage than the measured trip value for one phase.
6.
Measure the time delay for the TRST1 signal and compare it with the set value.
7.
Check the inverse time delay by injecting a voltage corresponding to 1.2 × Vpickup>.
8.
Repeat the test to check the inverse time characteristic at different over-voltage levels.
9.
Repeat the above described steps for Step 2 of the function.
11.6.2.2
Extended testing
1.
The tests above can be repeated for
11.6.2.3
Completing the test
continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.6.3
Two step residual overvoltage protection ROV2PTOV (59N)
Prepare the IED for verification of settings outlined in Section
settings".
11.6.3.1
Verifying the settings
1.
Apply a single-phase voltage either to a single-phase voltage input or to a residual voltage
input with the pickup value below the set value
2.
Slowly increase the value until PU_ST1 appears.
3.
Note the trip value and compare it with the set value.
4.
Decrease the voltage slowly and note the reset value.
5.
Set and apply a 20% higher voltage than the measured trip value for one phase.
6.
Measure the time delay for the TRST1 signal and compare it with the set value.
7.
Check the inverse time delay by injecting a voltage corresponding to 1.2 × Vpickup>.
( )
t s
IECEQUATION2429 V1 EN-US
Line distance protection REL670
Commissioning manual
>
VT
sec
´
´
VBase
100
VTprim
For example, if the inverse time curve A is selected, the trip signals TRST1 and
TRIP trip after a time corresponding to the equation:
k
1
=
U
1
>
U
1
© Copyright 2017 ABB. All rights reserved
2 out of 3 and for 3 out of 3 operation mode.
"Preparing the IED to verify
Pickup1 .
Testing functionality by secondary injection
(Equation 98)
GUID-BE4B4A36-CCEE-4020-B7DC-6A83A43D11F5 v2
TESTMODE setting to Disabled .
(Equation 99)
Section 11
M13806-43 v6
SEMOD54358-3 v7
SEMOD54358-35 v11
185