ABB Relion 670 Series Commissioning Manual page 161

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
11.4.13.2
Initiating ZCVPSOF automatically and setting mode to impedance
1.
Set
2.
Deactivate the switch onto fault BC input.
3.
Set the current and voltage inputs to lower than
second.
4.
Apply a three-phase fault condition corresponding to a fault at approximately 45% of the line
or with impedance at 50% of the used zone setting and current greater than 30% of
IBase .Apply a two-phase fault condition corresponding to a fault at approximately 45% of
the line or with impedance at 50% of the used zone setting and current greater than 30% of
IBase .
The ZACC input is activated.
5.
Check that the correct TRIP output, external signals and indication are obtained.
11.4.13.3
Initiating ZCVPSOF automatically and setting mode to VILevel
1.
Set
2.
Deactivate the switch onto fault BC input.
3.
Set the current and voltage inputs to lower than
second.
4.
Apply the three-phase currents in such a way that the magnitudes are greater than
and the three-phase voltages in such a way that the magnitudes and lower than
least for the duration of the
5.
Check that the correct TRIP output, external signals and indication are obtained.
11.4.13.4
Completing the test
continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.4.14
Phase preference logic PPLPHIZ
Prepare the IED for verification of settings outlined in Section
settings".
The Phase preference logic function PPLPHIZ is tested with a three-phase testing equipment for
distance protections. PPLPHIZ is tested in co-operation with the Distance protection zone,
quadrilateral characteristic function ZMQPDIS (21). The distance protection and the phase
preference logic shall be set to values according to the real set values to be used. The test is made
by means of injection of voltage and current where the amplitude of both current and voltage and
the phase angle between the voltage and current can be controlled.
During the test the following binary signals (outputs) shall be monitored:
Trip signal from distance protection
Trip signal from phase preference logic
Line distance protection REL670
Commissioning manual
AutoInitMode to Voltage and Mode to Impedance .
AutoInitMode to Voltage and Mode to VILevel .
© Copyright 2017 ABB. All rights reserved
IphPickup and UVPickup for at least one
IphPickup and UVPickup for at least one
tDuration setting.
Testing functionality by secondary injection
GUID-E83E1B3D-026C-48DB-BB9B-43C6597DE5DB v5
UVPickup at
TESTMODE setting to Disabled .
GUID-BD8EE7A0-710D-49C8-9B56-CB908BAF2C59 v7
"Preparing the IED to verify
Section 11
M13850-27 v8
IphPickup
M13850-41 v5
155