ABB Relion 670 Series Commissioning Manual page 130

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
Test point
5
6
7
8
9
10
11
12
13
Table
32
40% of RLdFwd
80% of RLdFwd
encroachment)
ANSI05000369 V2 EN-US
Figure 36: Distance protection characteristic with test points for phase-to-ground
Table
33
124
Reach
Set value
X
0.85 x RFPPZx x tan (LdAngle)
R
0.85 x RFPPZx
X
RLdFwd x tan (LdAngle)
R
RLdFwd
X
RLdFwd x tan (LdAngle)
R
0
X
–0.2143 x RFPPZx/2
R
0.8 x RFPPZx/2
X
–0.4 x RLdFwd x tan(ArgDir=20°)
R
0.4 x RLdFwd
X
0.5 x X1
set
R
–0.23 x X1
set
X
0.8 x X1
set
R
–0.37 x X1
set
X
0.5 x X1
set
R
0.5 x R1
set
X
0
R
0.5 x RFPPZx
is used in conjunction with figure 35.
2
1
11
10
12
120°
a
9
8
alt. 80% of
RFPG
RFPG (Load
measurements
is used in conjunction with figure 36.
© Copyright 2017 ABB. All rights reserved
Comments
LdAngle = angle for the maximal load transfer
Exact: 0.8 x RFPPZx/2 (ArgDir=20°)
Exact –0.5 x R1
Exact –0.5 x R1
80%
3
50%
4
5
6
7
13
20°
ANSI05000369-2-en.vsd
1MRK 506 371-UUS E
x tan(ArgNegRes=30°)
set
x tan(ArgNegRes=30°)
set
Line distance protection REL670
Commissioning manual