Section 14
Troubleshooting
Headline
Invalid value set for PMU Parameters
Invalid phase angle reference
GOOSE is configured on a disabled port
LDCM not running the application image
LDCM version is not accepted
OEM not running the application image
SFP unplugged from the slot
SFP replaced with other type
Non ABB vendor SFP detected
14.2.4
Hardware re-configuration
When adding, removing or moving a hardware modules in an IED ( for example, I/O modules,
communication modules or time synchronization modules) a set of procedures must be followed.
Adding a new module in to an IED
Procedure:
266
© Copyright 2017 ABB. All rights reserved
Explanation
There are two explanations possible:
Check if the following parameters are set correctly on
ReportRate or SvcClass or parameter
PMUREPORT:
PRIMVAL:1.FrequencySel is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
ReportRate or SvcClass or RptTimetag or
PMUREPORT:
parameter PRIMVAL:1.FrequencySel is not set as 50Hz /
60Hz.
PhaseAngleRef corresponds to an analog
The selected
channel that is not configured. Please configure a valid
reference channel.
At least one of the access points configured for GOOSE
is disabled. The port can be disabled either through
changing the access point operation to off or by
unchecking the GOOSE protocol from the access point
in the Ethernet configuration in PCM600 or LHMI.
Please enable GOOSE on access points: AP_FRONT,
AP_1
<slot number> is running the factory image instead of
the application image. The factory image is older and
does not contain the latest updates and fixes.
Please reboot the IED. If the problem persists update
the LDCM firmware or replace the board.
<device name> firmware version <version string> is not
accepted. The minimum accepted version is <version
string>.
Please update the LDCM firmware or replace the board.
OEM in slot <slot number> is running the factory image
instead of the application image. The factory image is
older and does not contain the latest updates and fixes.
Please reboot the IED. If the problem persists, update
the OEM firmware or replace the board.
SFP has been unplugged from the slot
Please check the connection.
Corresponding hardware(s) is set to fail.
Configured and the detected SFP(s) are different.
Corresponding hardware(s) is set to fail.
Please restart IED and consider Reconfigure HW
modules to get updated hardware list.
Non ABB vendor SFP detected.
Corresponding hardware(s) is set to fail. Please use
ABB approved SFP's.
Line distance protection REL670
1MRK 506 371-UUS E
GUID-334C5D8B-F383-4CDE-9850-659ED6B405DC v1
Commissioning manual