Entering settings

If the IED is connected to a monitoring or control system via the rear SPA/IEC103 port, the
SPA/IEC103 port has to be set either for SPA or IEC103 use.
6.1.1

Entering SPA settings

The SPA/IEC port is located on the rear side of the IED. Two types of interfaces can be used:
plastic fibers with connector type HFBR
glass fibers with connector type ST
When using the SPA protocol, the rear SPA/IEC port must be set for SPA use.
Procedure:
1.
Set the port for SPA use on the local HMI under Main menu /Configuration /
Communication /Station communication/Port configuration/SLM optical serial port/
PROTOCOL:1. When the communication protocol is selected, the IED is automatically
restarted, and the port then operates as a SPA port.
2.
Set the
menu/Configuration/Communication/Station communication/SPA/SPA:1. Use the
same settings for these as is set in the SMS system for the IED.
6.1.2

Entering IEC settings

The SPA/IEC port is located on the rear side of the IED. Two types of interfaces can be used:
plastic fibers with connector type HFBR
glass fibers with connector type ST
When using the IEC protocol, the rear SPA/IEC port must be set for IEC use.
Procedure:
1.
Set the port for IEC use on the local HMI under Main menu /Configuration /
Communication /Station communication/Port configuration/SLM optical serial port/
PROTOCOL:1. When the communication protocol is selected, the IED is automatically
restarted, and the port then operates as an IEC port.
2.
Set the
menu/Configuration/Communication/Station communication/IEC60870-5-103/
OPTICAL103:1. Use the same settings for these as is set in the SMS system for the IED.
Breaker protection REQ650
Commissioning manual
Establishing connection and
verifying the SPA/IEC
communication
SlaveAddress and BaudRate for the rear SPA port on the local HMI under Main
SlaveAddress and BaudRate for the rear IEC port on the local HMI under Main