Section 11
Testing functionality by secondary injection
where:
t(s)
TD1
V
Vpickup< Set pickup voltage for step 1
For example, if the measured voltage jumps from the rated value to 0.8 times the set pickup
voltage level and time multiplier TD1 is set to 0.05 s (default value), then the TRST1 and TRIP
signals trip at a time equal to 0.250 s ± tolerance.
10.
The test above can be repeated to check the inverse time characteristic at different voltage
levels.
11.
Repeat the above described steps for Step 2 of the function.
Extended testing
The tests above can be repeated for
11.6.1.2
Completing the test
continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.6.2
Two step overvoltage protection OV2PTOV (59)
Prepare the IED for verification of settings as outlined in section
section
"Preparing for test"
11.6.2.1
Verifying the settings
Verification of single-phase voltage and time delay to trip for Step 1
1.
Apply single-phase voltage below the set value
2.
Slowly increase the voltage until the PU_ST1 signal appears.
3.
Note the trip value and compare it with the set value
For phase-to-ground measurement:
Vpickup
ANSIEQUATION2426 V1 EN-US
For phase-to-phase measurement:
184
Trip time in seconds
Settable time multiplier of the function for step 1
Measured voltage
in this chapter.
The trip value in secondary volts is calculated according to the following
equations:
>
VBase
VT
sec
´
´
100
VTprim
3
© Copyright 2017 ABB. All rights reserved
2 out of 3 and for 3 out of 3 operation mode.
Pickup1 .
Pickup1 .
1MRK 506 371-UUS E
TESTMODE setting to Disabled .
"Requirements"
and
(Equation 97)
Line distance protection REL670
Commissioning manual
M13796-35 v8
M13796-25 v5
M13806-2 v6
M13806-9 v2
M13806-50 v9