ABB Relion 670 Series Commissioning Manual page 129

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
One phase-to-phase fault
One phase-to-ground fault
The shape of the operating characteristic depends on the values of the setting parameters.
X1
40% of RLdFwd
80% of RLdFwd
ANSI05000368 V1 EN-US
Figure 35: Distance protection characteristic with test points for phase-to-phase
Table 32:
Test point
1
2
3
4
Table continues on next page
Line distance protection REL670
Commissioning manual
The figures illustrating the characteristic for the distance protection function can
be used for settings with and without load encroachment. The solid lines designate
the diagram applicable when the load current compensation is active. The solid line
and all test points except 13 are valid for this case.
When the load current compensation is inactive, the dotted lines and test point 13
are valid. Test points 5, 6, and 7 are not valid for this measurement.
X
2
1
80%
11
50%
10
12
120°
a
7
9
8
0.5 x RFPP
measurements
Test points for phase-to-phase loops A-B (Ohm/Loop)
Reach
Set value
X
X1
set
R
0
X
X1
set
R
R1
set
X
0.8 x X1
set
R
0.8 x R1
+ RFPPZx/2
set
X
0.5 x X1
set
R
0.5 x R1
+ RFPPZx/2
set
© Copyright 2017 ABB. All rights reserved
3
4
5
6
(O/phase)
R
13
c
20°
ANSI05000368-1-en.vsd
Comments
Testing functionality by secondary injection
Section 11
123