ABB Relion 670 Series Commissioning Manual page 261

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
Section 12
12.1
Overview
Before starting this process, all individual devices that are involved in the fault clearance process
of the protected object must have been individually tested and must be set in operation. The
circuit breaker must be ready for an open-close-open cycle.
The directional test is performed when the protected object is energized and a certain amount of
load current is available. It is also necessary to know the flow of the load current (import or export,
i.e. forward or reverse) by help of the indication from an external instrument (energy-meter, or
SCADA information).
The design of the test procedure depends on the type of protection function to be tested. Some
items that can be used as guidelines are the following.
12.2
Testing the directionality of the distance protection
The test is performed by looking at the information given by the High speed distance protection
ZMFPDIS, ZMFCPDIS or the directional function ZDRDIR or ZDMRDIR whichever is used.
Procedure:
1.
Make sure that all control and protection functions that belong to the object that are going to
be energized have been tested and are set to be in operation
2.
Make sure that the primary load current fulfills the following conditions (by using an external
equipment):
The primary load impedance must have an angle (PHI) between the setting angles for the
directional lines. In case of default settings this means:
The settings for forward load: -
180 deg -
ZDMRDIR are available under the HMI menu:
3.
The directionality of the load current is shown by the High speed distance protection
ZMFPDIS or ZMFCPDIS under the HMI menu: Main menu/Test/Function status/Impedance
protection/HighSpeedDistance or by the directional function ZDRDIR or ZDMRDIR and it is
available under the HMI menu: Main menu/Test/Function status/Impedance protection/
DirectionalImpedance
Line distance protection REL670
Commissioning manual
Checking the directionality
The magnitude of the primary load current must be higher than the minimum operating
current set for the directional elements in the IED. In case of default settings this means:
load current > 5% of base current
Otherwise the settings
available under the HMI menu: Main menu/Settings/IED Settings/Impedance
protection/DirectionalImpedance
for forward (exported) load: -15 deg < PHI < 115 deg
for reverse (imported) load: 165 deg < PHI < 295 deg
ArgDir < PHI < 180 deg + ArgNegRes included in the directional functions ZDRDIR or
Main menu/Settings/IED Settings/Impedance protection/DirectionalImpedance
© Copyright 2017 ABB. All rights reserved
IMinOpPG and IMinOpPP for ZDRDIR or ZDMRDIR are
ArgDir < PHI < ArgNegRes and the settings for reverse load:
Section 12
Checking the directionality
GUID-7E504488-F341-477A-953A-EB0B262911EB v2
GUID-EB5380B2-6086-4814-8890-102E55A79C82 v4