ABB Relion 670 Series Commissioning Manual page 269

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
HMI Signal Name:
Time Sync
Application
RTE
IEC61850
LMD
LDCMxxx
OEM
Also the internal signals, such as INT--FAIL and INT--WARNING can be connected to binary output
contacts for signalling to a control room.
In the IED Status - Information, the present information from the self-supervision function can be
viewed. Indications of failure or warnings for each hardware module are provided, as well as
information about the external time synchronization and the internal clock. All according to table
47. Loss of time synchronization can be considered as a warning only. The IED has full functionality
without time synchronization.
When settings are changed in the IED, the protection and control applications restart in order to
take effect of the changes. During restart, internal events get generated and Runtime App error
will be displayed. These events are only indications and will be for short duration during the
restart.
14.2.2
Using front-connected PC
When an internal fault has occurred, extensive information about the fault can be retrieved from
the list of internal events available in the SMS part:
TRM-STAT TermStatus - Internal Events
Line distance protection REL670
Commissioning manual
Status
Description
READY / FAIL
This signal will be active when the
source of the time synchronization is
lost, or when the time system has to
make a time reset.
READY / FAIL
This signal will be active if one or
more of the application threads are
not in the state that Runtime Engine
expects. The states can be CREATED,
INITIALIZED, RUNNING, etc.
READY / FAIL
This signal will be active if the
Runtime Engine failed to do some
actions with the application threads.
The actions can be loading of settings
or parameters for components,
changing of setting groups, loading or
unloading of application threads.
READY / FAIL
This signal will be active if the IEC
61850 stack did not succeed in some
actions like reading IEC 61850
configuration, startup etc.
READY / FAIL
LON network interface, MIP/DPS, is in
an unrecoverable error state.
READY / FAIL
Line Differential Communication Error
status
READY / FAIL
Optical Ethernet Module error status
IED will not be operational during applications restart.
© Copyright 2017 ABB. All rights reserved
Section 14
Troubleshooting
M11763-203 v6
263