ABB Relion 670 Series Commissioning Manual page 77

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
IEC140000133 V1 EN-US
Figure 9:
The following steps explain how to set the PMU Connection Tester parameters in order to
establish an IEEE C37.118 connection with the PMU:
1.
Set the IP stack on PMU Connection Tester to IPv4. Note that the default IP stack on PMU
Connection Tester tool is IPv6.
Line distance protection REL670
Commissioning manual
PMU Connection Tester tool
© Copyright 2017 ABB. All rights reserved
Establishing connection and verifying the IEEE C37.118/1344 communication
IEC140000133-1-en.vsd
Section 9
71