Test with a frequency difference outside the set limits for manual and auto synchronizing check
respectively.
1.
Apply voltages V-Line equal to 100%
with a frequency difference equal to 0 mHz and a phase difference lower than the set value.
2.
Check that the AUTOSYOK and MANSYOK outputs are activated.
3.
Apply voltage to the V-Line equal to 100%
and voltage V-Bus equal to 100%
4.
Check that the two outputs are not activated. The test can be repeated with different
frequency values to verify that the function trips for values lower than the set ones. If a
modern test set is used, the frequency can be changed continuously.
Testing the reference voltage
1.
Use the same basic test connection as in figure 50.
The voltage difference between the voltage connected to V-Bus and V-Line should be 0%, so
that the AUTOSYOK and MANSYOK outputs are activated first.
2.
Change the V-Line voltage connection to V-Line2 without changing the setting on the local
HMI. Check that the two outputs are not activated.
11.10.1.3
Testing the energizing check
During the test of the energizing check function for a single bay arrangement, these voltage inputs
are used:
V-Line
V-Bus
General
When testing the energizing check function for the applicable bus, arrangement shall be done for
the energizing check functions. The voltage is selected by activation of different inputs in the
voltage selection logic.
Live voltage level is fixed to 80%
The test shall be performed according to the settings for the station. Test the alternatives below
that are applicable.
Testing the dead line live bus (DLLB)
The test should verify that the energizing check function trips for a low voltage on the V-Line and
for a high voltage on the V-Bus. This corresponds to the energizing of a dead line to a live bus.
1.
Apply a single-phase voltage 100%
30%
2.
Check that the AUTOENOK and MANENOK outputs are activated after set
respectively
3.
Increase the V-Line to 60%
The outputs should not be activated.
4.
The test can be repeated with different values on the V-Bus and the V-Line.
Line distance protection REL670
Commissioning manual
VA, VB or VC line1 voltage inputs on the IED
Bus voltage input on the IED
VBase and dead voltage level to fixed 40% VBase .
GblBaseSelLine to the V-Line.
tManEnerg .
GblBaseSelLine and V-Bus to be equal to 100% GblBaseSelBus .
© Copyright 2017 ABB. All rights reserved
GblBaseSelLine and V-Bus equal to 100% GblBaseSelBus ,
GblBaseSelLine with a frequency equal to 50 Hz
GblBaseSelBus , with a frequency outside the set limit.
GblBaseSelBus to the V-Bus, and a single-phase voltage
Testing functionality by secondary injection
tAutoEnerg