ABB Relion 670 Series Commissioning Manual page 163

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
1.
Connect the test set for injection of voltage and current.
2.
Inject voltages and currents corresponding to a phase-to-phase to ground fault within zone 1
of the distance protection function. In the test one of the current inputs (one of the faulted
phases) is disconnected. The remaining current is the fault current out on the protected line.
All combinations of two phase-to-ground faults with one phase current are tested. The result
shall be according to table 37. It should be checked that the fault will give phase-to-phase
voltage, phase-to-ground voltage, zero-sequence voltage and phase current so that the
conditions set for the logic are fulfilled.
Table 37:
OperMode
No Filter
No Pref
1231c
1321c
123a
132a
213a
231a
312a
321a
11.4.16
Completing the test
continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.5
Current protection
11.5.1
Instantaneous phase overcurrent protection 3-phase output
PHPIOC (50)
Prepare the IED for verification of settings outlined in Section
settings".
Values of the logical signals for PHPIOC are available on the local HMI under Main menu/Tests/
Function status/Current protection/InstPhaseOverCurrent(50,3I>>)/PHPIOC(50;3I>>):x, where x
= 1, 2, and 3.
The Signal Monitoring in PCM600 shows the same signals that are available on the local HMI.
To verify the settings the following fault type should be tested:
Phase-to-ground fault
Line distance protection REL670
Commissioning manual
Operation at different combinations of faults and operation mode
Fault type/Faulted phase current to the IED
A_BG/IA
A_BG/IB
Trip
Trip
Trip
Trip
Trip
No Trip
No Trip
Trip
Trip
No Trip
Trip
No Trip
No Trip
Trip
No Trip
Trip
Trip
No Trip
No Trip
Trip
© Copyright 2017 ABB. All rights reserved
B_CG/IB
B_CG/IC
C_CG/IA
Trip
Trip
Trip
Trip
Trip
Trip
Trip
No Trip
No Trip
No Trip
Trip
Trip
Trip
No Trip
Trip
No Trip
Trip
Trip
Trip
No Trip
Trip
Trip
No Trip
No Trip
No Trip
Trip
No Trip
No Trip
Trip
No Trip
Testing functionality by secondary injection
C_AG/IC
Trip
Trip
Trip
No Trip
No Trip
No Trip
No Trip
Trip
Trip
Trip
GUID-8BD66BC8-AAC3-41C4-B819-B159361688D2 v4
TESTMODE setting to Disabled .
"Preparing the IED to verify