ABB Relion 670 Series Commissioning Manual page 148

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
1.
Check the Application Configuration: verify that hardware voltage and current channels of the
IED are properly connected to SMAI function blocks, and that the proper analog outputs of
SMAI's are connected to the analog inputs of the function block OOSPPAM.
2.
Connect three-phase voltage channels of the test set to the appropriate IED terminals.
3.
Connect in parallel two groups of three-phase currents of the test set to the appropriate IED
terminals.
4.
Connect the appropriate trip output of the IED to the input channel of the test set that
monitors the trip.
5.
Go to Main menu/Settings/IED Settings/Impedance protection/OutOfStep(78,Ucos)/
OOSPPAM(78,Ucos):1, and make sure that the function is enabled, that is,
On .
11.4.12.2
Test of point RE (R
The trajectory of the impedance does not enter the lens characteristic.
Preliminary steady state test at 50 Hz
Go to Main menu/Test/Function status/Impedance protection/OutOfStep(78,Ucos)/
OOSPPAM(78,Ucos):1/Outputs to check the available service values of the function block
OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related to phase
L1):
V
=
ts
EQUATION14057 V1 EN-US
V
ts
EQUATION14058 V1 EN-US
frequency of V
I
50
s
EQUATION14059 V1 EN-US
∠I
50s
frequency of I
It
fs
EQUATION14062 V1 EN-US
∠I
tfs
frequency of I
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are according to the injected
quantities and that ROTORANG is close to 0 rad.
For this particular injection the service values are:
142
, X
FwdR
V
VT s
,
1 1
.
V
1 1 11931
.
×
×
=
×
t FwdZ
,
V
VT p
,
ForwardX
=
 =
arctan
arctan
ForwardR
= 50 Hz
ts
I
1
CTs
I
10459
=
×
=
×
50
I
9000
CTp
=0°
= 50 Hz
50s
I
1
CTs
I
10459
=
×
=
×
tf
I
9000
CTp
=0°
= 50 Hz
tfs
© Copyright 2017 ABB. All rights reserved
)
FwdX
0 1
.
95 1
.
V
×
=
13 8
.
59 33
.
 =
82. . 14°
8 19
.
= .
1 162
A
1 162
.
A
=
1MRK 506 371-UUS E
Operation is set to
GUID-911D370F-8767-4D6C-9621-8663DD26006C v1
GUID-5C5E9BEB-AA60-474E-ACEC-B972ACFE6FA2 v1
GUID-8F95CCCC-3282-48E8-9F5E-3F3E77CCCAAE v1
(Equation 17)
(Equation 18)
(Equation 19)
(Equation 20)
Line distance protection REL670
Commissioning manual