ABB Relion 670 Series Commissioning Manual page 235

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
4.
Abruptly reverse the current to
directional element.
5.
Check that the IRVL output still is activated after the reversal with a time delay that complies
with the setting
6.
Switch off the polarizing voltage and the current.
11.11.6.2
Testing the weak-end infeed logic
If setting
1.
Inject the polarizing voltage 3V0 to (180° —
voltage and current to 155°, the current leads the voltage.
2.
Inject current (180° —
INDir ).
(
3.
Activate the CRL binary input.
4.
Abruptly reverse the current to the setting of
the forward directional element.
5.
Switch off the current and check that the ECHO and CS appear on the corresponding binary
output during 200ms after resetting the directional element.
6.
Switch off the CRL binary input.
7.
Activate the BLOCK binary input.
8.
Activate the CRL binary input.
9.
Switch off the polarizing voltage and reset the BLOCK and CRL binary input.
If setting
1.
Inject the polarizing voltage 3V0 to about 90% of the setting (
2.
Activate the CRL binary input.
3.
Increase the injected voltage to about 110% of the setting (
4.
Activate the CRL binary input.
Line distance protection REL670
Commissioning manual
tDelayRev .
WEI = Echo
AngleRCA ) in one phase to about 110% of the setting operating current
No ECHO and CS should appear.
No ECHO and CS should appear.
No ECHO and CS should appear.
WEI = Echo & Trip
No ECHO, CS and TRWEI outputs should appear.
© Copyright 2017 ABB. All rights reserved
AngleRCA setting lagging the voltage, to operate the forward
AngleRCA ) of VBase and the phase angle between
AngleRCA setup lagging the voltage, to operate
Testing functionality by secondary injection
3V0PU ) operating voltage.
3V0PU ) operating voltage.
Section 11
M13936-25 v2
M13936-27 v8
M13936-52 v12
229