1MRK 506 371-UUS E
The communication speed of the LON bus is set to the default of 1.25 Mbit/s. This can be changed
by LNT.
The LON communication setting parameters are set via the local HMI. Refer to the Technical
manual for more detailed specifications.
If LON communication from the IED stops because of illegal communication parameter settings
(outside the setting range) or due to other kind of disturbance, it is possible to reset the IED's
LON port.
LON communication setting parameters (Table 15) and LON node information parameters (Table
16) can only be set via the LON Network Tool (LNT).
Some of these parameters can be viewed on the local HMI under Main menu/Configuration/
Communication/Station communication/Port configuration/SLM optical LON port/LONGEN:1.
Table 15:
Parameter
DomainID
SubnNetAddr*
NodeAddr*
*Can be viewed on the local HMI
Table 16:
Parameter
NeuronID*
Location
*Can be viewed on the local HMI
ADE settings are available on the local HMI under Main menu/Configuration/Communication/
Station communicaton/LON/ADE:1
Table 17:
Name
Operation
TimerClass
LON commands are available on the local HMI under Main menu/Configuration/Communication/
Station communication/Port configuration/SLM optical LON pot/Service Pin Messae/Generate
service pin message
Line distance protection REL670
Commissioning manual
LON communication setting parameters
Range
Default
0
0
0 - 255
0
Step: 1
0 - 127
0
Step: 1
LON node information parameters
Range
Default
0 - 12
Not loaded
0 - 6
No value
ADE Non group settings (basic)
Values (Range)
Disabled
Enabled
Slow
Normal
Fast
© Copyright 2017 ABB. All rights reserved
Establishing connection and verifying the LON communication
Unit
Parameter description
-
Domain identification number
-
Subnet address
-
Node address
Unit
Parameter description
-
Neuron hardware identification number in
hexadecimal code
-
Location of the node
Unit
Step
-
-
-
-
Default
Description
Disabled
Operation
Slow
Timer class
Section 7
M11888-3 v5
M11643-1 v4