ABB Relion 670 Series Commissioning Manual page 211

Line distance protection
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 506 371-UUS E
Step No.
3-b
3-a
3-b
4.
Repeat Step
11.9.4.2
Completing the test
Continue to test another function or end the test by changing the
Restore connections and settings to their original values, if they were changed for testing
purposes.
11.9.5
Current based delta supervision DELISPVC(7I)
Prepare the IED for verification of settings outlined in Section
settings".
11.9.5.1
Verifying the signals and settings
Make sure that the function is connected to SMAI function with I3P signal.
Delta supervision function has four different modes of operation. Proceed as follows to test the
function in a particular mode.
1.
Set the following parameters:
2.
Set the constant current input of IL1 = 1A at 0° and IL2 = 1A at 120° and IL3 at -120° secondary
at rated frequency.
3.
Based on the mode of operation, carry out the following changes on input condition of Step
to detect pickup condition.
Each mode is given for increase and decrease operation. (3-a and 3-b)
Line distance protection REL670
Commissioning manual
OpMode
RMS or DFT Mag
DFT Angle (vector
shift)
DFT Angle (Vector
shift)
3
with UL2 changes for different mode.
Operation = ON
MeasMode = Phase-to-ground
Imin = 10% of IBase
DelI> = 80% of IBase
DeltaT = 2
tHold = 100
© Copyright 2017 ABB. All rights reserved
Changes after step 2
Change UL1 back to 63.5V
Change UL1 to 63.5V at 15°
without changing
frequency
Change UL1 to 63.5V at 0°
without changing
frequency
Testing functionality by secondary injection
Expected output
STL1 , STRISE, BFI_3P signal should be TRUE
for 100 ms
STL1, BFI_3P signal will be TRUE for 100 ms.
STL1, BFI_3P signal will be TRUE for 100 ms
GUID-2FE5E5F0-0E6C-499E-93D2-471C183B89BF v2
TestMode setting to Disabled .
GUID-9EAEFF02-62C2-4FA7-8F3D-E92391206F7F v2
"Preparing the IED to verify
GUID-86324E4D-E054-495F-9D64-29741FBD8CBE v2
Section 11
2
205