Figure 26: Operating characteristic for phase selection function, forward direction phase-
Table 23:
Test point
1
2
3
4
5
6
Table
23
Line distance protection REL670
Commissioning manual
is used together with figure 25.
(
X
1
4
85%
ArgNegRes
6
50% RLdFwd
0.5·RFltFwdPP
to-phase faults
Test points for phase-to-phase loops A-B (Ohm/phase)
Reach
Value
X
X1
R
0
X
0
R
RLdFwd
R
0.5·RFLdFwPP
X
0.85·X1
R
0.85·X1·1/tan(60°)+0.5
RFLdFwdPP
X
0.85·X1
R
-0.85·X1·tan (AngNegRes-90°)
X
0.5·RFLdFwdPP·tan (ArgLd)
R
0.5·RFLdFwdPP
X
-0.5·RLdFwd·tan (ArgDir)
R
0.5·RLdFwd
is used together with figure 26.
© Copyright 2017 ABB. All rights reserved
W
/
phase
)
3
LdAngle
5
60°
2
7
ArgDir
ANSI09000735-1-en.vsd
Comments
When RLdFWd < 0,5·RFLdFwPP
When RLdFwd > 0,5·RFLdFwPP
R=0.491·X1+0.5 RFLdFwdPP
Can be limited by RFLdFwPP
Only when RLdFwd < RFLdFwPP
Testing functionality by secondary injection