Establishing connection and verifying the IEEE C37.118/1344 communication
3.3.
3.4. Set the
3.5.
3.6. Continue to the section
9.5

Verifying the communication

Connect your PC to the substation network and ping the connected IED and the Substation Master
PC, to verify that the communication is working (up to the transport layer). Make sure that the
optical fibers are connected correctly.
After checking the communication, it is time to verify the IEEE C37.118/1344 communication over
both TCP and UDP protocols.
One way to verify the communication up to the application layer is to use a protocol analyzer
connected to the substation bus, and monitor the communication. Alternatively, the PMU
Connection Tester tool can be used to verify the IEEE C37.118/1344 communication. The section
Setting the TCP/UDP client communication
parameters in order to establish an IEEE C37.118 connection with the PMU.
9.5.1

Verifying the IEEE C37.118/1344 TCP communication

After setting both PMU configuration and the TCP client configuration (As explained in sections
Setting the PMU station communication (PMU
(PMU configuration)
Ethernet communication is set up, click
74
IEC140000137 V1 EN-US
Host IP as the PMU IP address configured for the port in use. Here the LANAB:1
Set the
IPAddress (192.168.1.10) is set.
Port as the TCP port defined in the PMU for control of data sent over UDP client
group 1 (Default value: 4713). This can be found under the parameter
TCPportUDPdataCtrl1 as one of the UDP communication parameters.
Save the Alternate Command Channel Configuration settings.
and
Setting the TCP/UDP client
© Copyright 2017 ABB. All rights reserved
Verifying the IEEE C37.118/1344 UDP communication
explains how to set the PMU Connection Tester
Report),
Setting the PMU station communication
communication) and making sure that the
Connect on the PMU Connection Tester tool.
1MRK 506 371-UUS E
IEC140000137-1-en.vsd
GUID-D10769FC-6C70-48A3-A1D8-FAFCCA82A3BE v2
GUID-289E2E92-431E-45FE-B586-A723588B98A1 v1
Line distance protection REL670
Commissioning manual