2.1.1 Power LED indicator

When the data logger is powered, the Power LED will turn on according to power and program
states:
Off: No power, no program running.
l
1 flash every 10 seconds: Powered from BAT, program running.
l
2 flashes every 10 seconds: Powered from CHG, program running.
l
3 flashes every 10 seconds: Powered via USB, program running.
l
Always on: Powered, no program running.
l

2.2 Power output

The data logger can be used as a power source for communications devices, sensors and
peripherals. Take precautions to prevent damage to these external devices due to over- or under-
voltage conditions, and to minimize errors. Additionally, exceeding current limits causes voltage
output to become unstable. Voltage should stabilize once current is again reduced to within
stated limits. The following are available:
Continuous 12 V: BAT + and – provide a connection to the unregulated, nominal 12 VDC
l
battery. It may rise above or drop below the power requirement of the sensor or peripheral.
SW12: program-controlled, switched 12 VDC terminal. It is often used to power devices
l
such as sensors that require 12 VDC during measurement. Voltage on a SW12 terminal will
change with data logger supply voltage. CRBasic instruction
terminal. See the CRBasic Editor help for detailed instruction information and program
examples:
https://help.campbellsci.com/crbasic/cr300/.
VX terminals: supply precise output voltage used by analog sensors to generate high
l
resolution and accurate signals. In this case, these terminals are regularly used with
resistive-bridge measurements (see
SWVX()
Using the
regulated 3.3 or 5 VDC power source to power digital sensors and toggle control lines.
C, SE 1-4, and P_SW terminals: can be set low or high as output terminals (SE 1-4 and P_SW
l
to 3.3 V, and C to 5 V). With limited drive capacity, digital output terminals are normally
used to operate external relay-driver circuits. Drive current and high-state voltage levels
vary between terminals. See also
See also
Power requirements
Resistance measurements
instruction, VX terminals can also supply a selectable, switched,
Digital input/output specifications
(p. 184).
SW12()
controls the SW12
(p. 72) for more information).
(p. 192).
2. Wiring panel and terminal functions
9