referenced by this setting cannot contain a
names or tables that are defined in the main program file.
This setting must specify both the name of the file to run as well as on the device (CPU:) on
which the file is located. The extension of the file must also be valid for a data logger program
(.CRB, .DLD, .CR300).
String data type
l

18.3.19 IPAddressEth

Specifies the IP address used by the Ethernet interface. If this value is specified as "0.0.0.0" (the
default), the data logger will use DHCP to configure the effective value for this setting as well as
the Ethernet Default Gateway and Ethernet Subnet Mask settings. This setting is
the equivalent to the IPAddressEth status table variable.
String data type
l

18.3.20 IPGateway

Specifies the IP address of the network gateway on the same subnet as the Ethernet interface. If
the value of the Ethernet IP Address setting is set to "0.0.0.0" (the default), the data logger will
configure the effective value of this setting using DHCP. This setting is the equivalent to the
IPGateway
status table variable.
String data type
l

18.3.21 IPMaskEth

Specifies the subnet mask for the Ethernet interface. If the value of the Ethernet IP Address
setting is set to "0.0.0.0" (the default), the data logger will configure the effective value of this
setting using DHCP.
String data type
l

18.3.22 IPMaskWiFi

Specifies the subnet mask for the WiFi interface.
String data type
l

18.3.23 IPTrace

Discontinued; aliased to IPTraceComport
BeginProg()
statement or define any variable