Pppinterface; Pppipaddr; Ppppassword; Pppusername - Campbell CR300 Series Product Manual

Compact datalogger
Hide thumbs Also See for CR300 Series:
Table of Contents

Advertisement

18.3.40 pppInterface

This setting controls which data logger port PPP service will be configured to use.

18.3.41 pppIPAddr

Specifies the IP address that will be used for the PPP interface if that interface is active (the PPP
Interface setting needs to be set to something other than Inactive).
String data type
l

18.3.42 pppPassword

Specifies the password that will be used for PPP connections when the value of PPP Interface is
set to something other than Inactive.
String data type
l

18.3.43 pppUsername

Specifies the user name that is used to log in to the PPP server.
String data type
l

18.3.44 RouteFilters

This setting configures the data logger to restrict routing or processing of some PakBus message
types so that a "state changing" message can only be processed or forwarded by this data logger
if the source address of that message is in one of the source ranges and the destination address
of that message is in the corresponding destination range. If no ranges are specified (the
default), the data logger will not apply any routing restrictions. "State changing" message types
include set variable, table reset, file control send file, set settings, and revert settings.
If a message is encoded using PakBus encryption, the router will forward that message regardless
of its content. If, however, the routes filter setting is active in the destination node and the
unencrypted message is of a state changing type, the route filter will be applied by that end
node.
String data type
l
18. Information tables and settings (advanced)