32-Bit Floating Point; Modbus Tips And Troubleshooting; Error Codes; Result Code -01: Illegal Function - Campbell CR300 Series Product Manual

Compact datalogger
Hide thumbs Also See for CR300 Series:
Table of Contents

Advertisement

32-Bit floating point

32-bit floating point values use 2 registers each. This is the default FLOAT data type in Campbell
Scientific data loggers. Select the appropriate ModbusOption to avoid post-processing.

15.2.8 Modbus tips and troubleshooting

Most of the difficulties with Modbus communications arise from deviations from the standards,
which are not enforced within Modbus. Whether you are connecting via Modbus to a solar
inverter, power meter, or flow meter, the information provided here can help you overcome the
challenges, and successfully gather data into a Campbell data logger. Further information on
Modbus can be found at:
www.simplyModbus.ca/FAQ.htm
l
www.Modbus.org/tech.php
l
www.lammertbies.nl/comm/info/modbus.html
l

15.2.8.1 Error codes

Modbus defines several error codes, which are reported back to a master from a slave.
ModbusMaster()
no response was received.

Result code -01: illegal function

The illegal function error is reported back by a Modbus slave when either it does not support the
function at all, or does not support that function code on the requested registers. Different
devices support different functions (consult the device documentation). If the function code is
supported, make sure you are not trying to write to a register labeled as read-only. It is common
for devices to have holding registers where read-only and read/write registers are mapped next to
each other.
An uncommon cause for the -01 result is a device with an incomplete implementation of
Modbus. Some devices do not fully implement parsing Modbus commands. Instead, they are
hardcoded to respond to certain Modbus messages. The result is that the device will report an
error when you try selectively polling registers. Try requesting all of the registers together.

Result code -02: illegal data address

The illegal data address error occurs if the slave rejects the combination of starting register and
length used. One possibility, is a mistake in your program on the starting register number. Refer
to the earlier section about register number and consult the device documentation for support
information. Also, too long of a length can trigger this error. The
displays these codes as a negative number. A positive result code indicates
ModbusMaster()
15. Communications protocols
instruction
95