18.2.12 MaxProcTime

Maximum time (μs) required to run through processing for the current scan. Value is reset when
the scan exits. Enter 0 to reset. Updated at the conclusion of scan processing, prior to waiting for
the next scan.

18.2.13 MaxSlowProcTime

Maximum time (μs) required to run through processing for the current Slow Sequence scan.
Value is reset when the scan exits. Enter 0 to reset. Updated at the conclusion of scan processing,
prior to waiting for the next scan.

18.2.14 MeasureTime

Reports the time (μs) needed to make measurements in the current scan. Calculated at compile
time. Includes integration and settling time. Assumes all measurement instructions will run each
scan. Updated when a main scan begins.

18.2.15 MemoryFree

Unallocated final-data memory on the CPU (bytes). All free memory may not be available for
data tables. As memory is allocated and freed, holes of unallocated memory, which are unusable
for final-data memory, may be created. Updated after compile completes.

18.2.16 MemorySize

Total final-data memory size (bytes) in the CR300 series. Updated at startup.

18.2.17 OSDate

Release date of the operating system in the format mm/dd/yyyy. Updated at startup.
String data type
l

18.2.18 OSSignature

Signature of the operating system.

18.2.19 OSVersion

Version of the operating system in the CR300 series. Updated at OS startup.