VLT AQUA High Power Instruction Manual

3.6.14 Fuses

Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines, etc., must be short-
circuited and overcurrent protected according to national/international regulations.
Short-circuit protection:
The adjustable frequency drive must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using the fuses mentioned
below to protect service personnel and equipment in case of an internal failure in the drive. The adjustable frequency drive provides full short-circuit
protection in case of a short-circuit on the motor output.
Overcurrent protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. The adjustable frequency drive is equipped with
internal overcurrent protection that can be used for upstream overload protection (UL applications excluded). See par. 4-18
fuses or circuit breakers can be used to provide the overcurrent protection in the installation. Overcurrent protection must always be carried out according
to national regulations.
Non-UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to the adjustable frequency drive.
P110 - P250
P315 - P450
380–480 V, frame sizes D, E and F
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240 V, or 480 V, or 500 V, or 600 V depending on
the drive voltage rating. With the proper fusing, the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Bussmann
Bussmann
Size/
E1958
E4273
Type
JFHR2**
T/JDDZ**
P110
FWH-
JJS-
300
300
P132
FWH-
JJS-
350
350
P160
FWH-
JJS-
400
400
P200
FWH-
JJS-
500
500
P250
FWH-
JJS-
600
600
Table 3.4: Frame size D, Line fuses, 380–480 V
Size/Type
Bussmann PN*
P315
170M4017
P355
170M6013
P400
170M6013
P450
170M6013
Table 3.5: Frame size E, Line fuses, 380–480 V
Size/Type
Bussmann PN*
P500
170M7081
P560
170M7081
P630
170M7082
P710
170M7082
P800
170M7083
P1M0
170M7083
Table 3.6: Frame size F, Line fuses, 380–480 V
380–480 V
380–480 V
SIBA
LittelFuse
E180276
E71611
JFHR2
JFHR2**
2061032.315
L50S-300
2061032.35
L50S-350
2061032.40
L50S-400
2061032.50
L50S-500
2062032.63
L50S-600
Rating
700 A, 700 V
6.9URD31D08A0700
900 A, 700 V
6.9URD33D08A0900
900 A, 700 V
6.9URD33D08A0900
900 A, 700 V
6.9URD33D08A0900
Rating
1600 A, 700 V
1600 A, 700 V
2000 A, 700 V
2000 A, 700 V
2500 A, 700 V
2500 A, 700 V
®
MG.20.P3.22 - VLT
is a registered Danfoss trademark
Ferraz-
Bussmann
Bussmann
Shawmut
E4274
E125085
E60314
H/JDDZ**
JFHR2*
JFHR2**
A50-P300
NOS-
170M3017
300
A50-P350
NOS-
170M3018
350
A50-P400
NOS-
170M4012
400
A50-P500
NOS-
170M4014
500
A50-P600
NOS-
170M4016
600
Ferraz
Siba
20 695 32.1600
20 695 32.1600
20 695 32.2000
20 695 32.2000
20 695 32.2500
20 695 32.2500
3 How to Install
Current Limit
. Moreover,
type gG
type gR
Internal
Option
Bussmann
170M3018
170M3018
170M4016
170M4016
170M4016
Siba
20 610 32.700
20 630 32.900
20 630 32.900
20 630 32.900
Internal Bussmann Option
170M7082
170M7082
170M7082
170M7082
170M7083
170M7083
3-59