6 General Specifications
1) For type of fuse, see the section
2) American Wire Gauge.
3) Measured using 16.4 ft [5 m] shielded motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerance relates to variety in voltage and cable
conditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss
in the adjustable frequency drive and opposite. If the switching frequency is increased compared to the default setting, the power losses may
rise significantly.LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the
losses. (Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
6
6-14
Fuses.
®
MG.20.P3.22 - VLT