5 How to program the adjustable frequency
drive
0-72 Time Format
Option:
[0] *
24 h
[1]
12 h
0-74 DST/Summertime
Option:
[0] *
OFF
5
[2]
Manual
0-76 DST/Summertime Start
Range:
Application
[Application dependant]
dependent*
0-77 DST/Summertime End
Range:
Application
[Application dependant]
dependent*
5.2.3 General Settings, 1-0*
Define whether the adjustable frequency drive operates in open-loop or closed-loop.
1-00 Configuration Mode
Option:
[0] *
Open-loop
[3]
Closed-loop
NOTE!
This parameter cannot be changed when the motor is running.
NOTE!
When set for closed-loop, the commands reversing and start reversing will not reverse the direction of the motor.
5-14
Function:
Sets the time format to be used in the LCP.
Function:
Choose how Daylight Saving Time/Summertime should be handled. For manual DST/Summertime
enter the start date and end date in par. 0-76
time End
.
Function:
Function:
Function:
Motor speed is determined by applying a speed reference or by setting desired speed when in hand
mode.
Open-loop is also used if the adjustable frequency drive is part of a closed-loop control system based
on an external PID controller providing a speed reference signal as output.
Motor speed will be determined by a reference from the built-in PID controller varying the motor
speed as part of a closed-loop control process (e.g., constant pressure or flow). The PID controller
must be configured in par. 20-** or via the function set-ups accessed by pressing the [Quick Menu]
button.
®
MG.20.P3.22 - VLT
is a registered Danfoss trademark
VLT AQUA High Power Instruction Manual