drive
Data transfer from LCP to adjustable frequency drive:
LCP Copy
1.
Go to par. 0-50
2.
Press the [OK] key.
3.
Select "All from LCP"
4.
Press the [OK] key.
The parameter settings stored in the GLCP are now transferred to the adjustable frequency drive, as indicated by the progress bar. When 100% is reached,
press [OK].
4.1.11 Initialization to Default Settings
4
There are two ways to initialize the adjustable frequency drive to default: Recommended initialization and manual initialization.
Please be aware that they have different impacts according to the below description.
Recommended initialization (via par. 14-22
1.
Select par. 14-22
2.
Press [OK]
3.
Select "Initialization" (for NLCP select "2")
4.
Press [OK]
5.
Disconnect the power from the unit and wait for the display to
turn off.
6.
Reconnecting the power resets the adjustable frequency drive.
Please note that the first start-up takes a few more seconds.
7.
Press [Reset]
NOTE!
Parameters selected in par. 0-25
Manual initialization
NOTE!
When carrying out manual initialization, serial communication, RFI filter settings and fault log settings are reset.
Removes parameters selected in par. 0-25
1. Disconnect from the line power and wait until the display
turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time as
powering up the Graphical LCP (GLCP).
2b. Press [Menu] while the LCP 101, Numerical Display is pow-
ering up.
3. Release the keys after 5 s.
4. The adjustable frequency drive is now programmed according
to default settings.
4-12
Operation Mode
Operation Mode
My Personal Menu
My Personal Menu
MG.20.P3.22 - VLT
VLT AQUA High Power Instruction Manual
)
Operation Mode
par. 14-22
RFI 1
par. 14-50
par. 8-30
Protocol
Address
par. 8-31
par. 8-32
Baud Rate
Minimum Response Delay
par. 8-35
Max Response Delay
par. 8-36
par. 8-37
Maximum Inter-Char Delay
Operating Hours
par. 15-00
par. 15-20
Historic Log: Event
Alarm Log: Error Code
par. 15-30
will remain present with the default factory setting.
This parameter initializes all except:
par. 15-00
Operating Hours
Power-ups
par. 15-03
par. 15-04
Over Temps
Over Volts
par. 15-05
®
is a registered Danfoss trademark
initializes all except:
Over Volts
to par. 15-05
to par. 15-22
Historic Log: Time
Alarm Log: Time
to par. 15-32