VLT AQUA High Power Instruction Manual
Line Power Supply 3 x 525–690 V AC
Typical Shaft output at 550 V
[kW]
Typical Shaft output at 575 V
[HP]
Typical Shaft output at 690 V
[kW]
Enclosure IP21
Enclosure IP54
Enclosure IP00
Output current
Continuous
(at 550 V) [A]
Intermittent (60 sec overload)
(at 550 V) [A]
Continuous
(at 575/690 V) [A]
Intermittent (60 sec overload)
(at 575/ 690V) [A]
Continuous KVA
(at 550 V) [KVA]
Continuous KVA
(at 575 V) [KVA]
Continuous KVA
(at 690 V) [KVA]
Max. input current
Continuous
(at 550 V) [A]
Continuous
(at 575 V) [A]
Continuous
(at 690 V) [A]
Max. cable size, line power, mo-
tor and load share [mm
Max. cable size, brake [mm
(AWG)]
Max. external pre-fuses [A]
Estimated power loss
at rated max. load [W]
Estimated power loss
at rated max. load [W]
Weight,
enclosure IP21, IP 54 [kg]
Weight,
enclosure IP00 [kg]
Efficiency
Output frequency
Heatsink overtemp. trip
Power card ambient trip
P315
250
350
315
D2
D2
D4
360
396
344
378
343
343
411
355
339
352
2 x 185
2
(2 x 350 mcm)
(AWG)]
2
2 x 185
(2 x 350 mcm)
1
500
5493
4)
, 575 V
5821
4)
, 690 V
151
138
4)
0–600 Hz
230°F [110°C]
140°F [60°C]
®
MG.20.P3.22 - VLT
is a registered Danfoss trademark
6 General Specifications
P400
P450
315
355
400
450
400
450
D2
E1
D2
E1
D4
E2
418
470
460
517
400
450
440
495
398
448
398
448
478
538
408
453
390
434
400
434
2 x 185
4 x 240
(2 x 350 mcm)
(4 x 500 mcm)
2 x 185
2 x 185
(2 x 350 mcm)
(2 x 350 mcm)
550
700
5852
6132
6149
6440
165
263
151
221
0.98
0–500 Hz
0–500 Hz
230°F [110°C]
185°F [85°C]
140°F [60°C]
154°F [68°C]
6
6-11
Need help?
Do you have a question about the VLT AQUA and is the answer not in the manual?
Questions and answers