Specification

Basic specifications
Rated voltage
DC24V
Range of power
Power supply for input and controlling GW/SI: DC24V
supply voltage
Power supply for output: DC24V+10%/-5% ( Voltage drop
warning at around 20V )
Rated current
Power supply for input and controlling GW/SI: 3.0A
(
Inside GW unit: 0.2A
Input device and SI control section: 2.8A
Power supply for solenoid valves and output: 3A
Number of input/
Input point: max. 64/Output point: max 64
output points
Higher-level bus
Protocol
DeviceNet Release 2.0
Slave ( slave station ) type
Group2 only server
MAC ID setting range
0 - 63
Device information
Vender code: 7 ( SMC Corp. )
Product type: 12 ( communication adapter )
Product code: 5001
Applicable message
Duplicate MAC ID check message
Group2 only unconnected explicit message
Explicit message
Poll I/O message
I/O message size
Input:
Output:
Date rate
125kbps, 250kbps, 500kbps
Transmission distance
Refer to the next page.
Insulation method
Photocoupler
8
10%
)
8 bytes
8 bytes
Transmission distance
DeviceNet allows T-branch, multi-branch and drop line branch connections.
Total extended length of trunk line and drop lines depends on the date rate and the
thickness of communication cable. The connection type for EX500 series is
T-branch only.
Terminating
resistor
Multi-branch
Node
Multi-branch
Drop
line
Node
Node
Node
Network length
Item
Maximum
Thick cable
network length
Thin cable
Total drop line length
Terminating resistor
Terminating
T-branch
resistor
Trunk line
Max.
Node
Drop line branch
6m
Node
Drop
Multi-
line
branch
Node
Node
Drop
line
Node
Date rate ( kbps )
125
250
500m or less
250m or less
100m or less
156m or less
78m or less
Note: Maximum length per drop line is 6m.
121
, 1/2W ( brown/red/brown/black/brown )
500
100m or less
39m or less
9