Replacing modules (spare part scenario)

7.2.1

Parts replacement for SIMOTION D4x5-2

Kernel/firmware ≥ V4.3
As of SIMOTION V4.3, a module replacement is detected by the controller on the basis of
the serial number. This automatically deletes the non-volatile data and transfers the data
backed up on the CompactFlash card to the controller. See Section Module replacement
(Page 103).
Kernel/firmware V4.2
If a used D4x5-2 is used for the module replacement, we recommend that the non-volatile
SIMOTION data be deleted on the used D4x5-2.
Two options are available for this.
Table 7- 1
Option
Module memory reset
Deleting and restoring non-
volatile SIMOTION data
NOTICE
With a Power OFF/ON, "Restore factory settings" is performed instead of "Memory reset" in
switch position "3" (MRES) of the mode selector switch.
Restore factory settings deletes all the project data on the CompactFlash card!
To avoid and unintentional/accidental deletion of the project data on the CompactFlash
card, we recommend that the non-volatile SIMOTION data be deleted via the Service
selector switch.
See also
Operations and their effect on the user memory (Page 94)
SIMOTION D4x5-2
Commissioning and Hardware Installation Manual, 02/2012
Options for deleting non-volatile SIMOTION data
Reference to description
Memory reset of SIMOTION
D4x5-2 (Page 285)
Deleting/restoring non-volatile
SIMOTION data (Page 368)
Service and maintenance
7.2 Replacing modules (spare part scenario)
Information
Controller via mode selector
switch (position "3" MRES). Is
available on all SIMOTION
platforms.
Controller via Service switch
(position "1").
Is only available on SIMOTION
D.