11. SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
This part contains all controller parameters, in which partial parameters only can be configured by PC
software.
11.1
BUSBAR SETTING
No.
Items
Bus
1
Rated Voltage
2
Rated Frequency
3
Volt.
4
Trans.(PT)
5
6
7
8
Over Voltage 1
Set
9
10
Over Voltage 2
11
Set
12
13
Over Voltage 3
14
Set
HMC6 Power Management Controller User Manual
Table 19 – Busbar Parameter Settings
Parameter Range
(30-30000)V
(10.0-75.0)Hz
(0-1)
Action
0: Disable
1: Enable
PT Primary (30-30000)V
PT
(30-1000)V
Secondary
(0-1)
Action
0: Disable
1: Enable
Set value
(90-150)%
Delay
(0.1-100.0)s
(0-5)
0: Block
1: Warn
Alarm Type
2: Trip
3: Shutdown
4: Safety Trip
5: Safety Stop
(0-1)
Action
0: Disable
1: Enable
Set value
(90-150)%
Delay
(0.1-100.0)s
Alarm Type (0-5)
(0-1)
Action
0: Disable
Default
Standard for checking busbar
over/under voltage. (It is primary voltage
when using voltage transformer; it is line
230
voltage when AC system is 3P3W while
it is phase voltage when using other AC
system).
Standard for checking busbar
50.0
over/under frequency.
0:Disable
Users can set the primary voltage and
secondary voltage of the voltage
100
transformer.
100
1:Enable
110
5.0
1:Warning
Setting value is busbar rated voltage's
percentage, and both return value and
delay value can be set.
1:Enable
120
3.0
2:Trip
0:Disable
Description
Page 46 of 87