8

SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

8.1 CONTENTS AND SCOPES OF PARAMETERS

Table 13 Parameter Configuration Contents and Range
No.
Items
Module Setting
1.
Power On Mode
2.
Module Address
3.
Language
4.
Password
Daylight Saving
5.
Time
6.
Date and Time
7.
Temperature Unit
8.
Pressure Unit
9.
Backlight Time
10.
Network
11.
J1939-75
12.
Alarm Data Interv.
13.
Custom Protocol
14.
Fn Function
Mains Setting
1.
Mains Options
2.
AC System
HGM9420N_HGM9420LT Genset Controller
HGM9420N_HGM9420LT GENSET CONTROLLER USER MANUAL
Parameters
Defaults
(0-2)
0
(1-254)
1
(0-2)
0
(0-65535)
00318
(0-1)
0
(0-1)
0
(0-2)
0
(0-3600)s
300
(0-1)
1
(0-1)
0
(0-60.0)s
0.1
(0-1)
0
(0-6)
0
(0-2)
1
(0-3)
0
2019-12-10
Description
0: Stop Mode
1: Manual Mode
2: Auto Mode
Controller address for remote monitoring
0: Simplified Chinese
1: English
2: Other
It is used to enter advanced parameter
setting.
0: Disable
1: Enable
Start and end time for this can be set.
It is used for date and time settings.
0: ℃; 1: ℉
0: kPa 1: psi 2: bar
0: Disable
1: Enable
0: Disable
1: Enable
0: Disable
1: Enable
0: Fn Button
1: Stop Button
2: Start Button
3. Manual Button
4. Auto Button
5: Mains Load Btn
6: Gen Load Btn
0: Disable; 1: AMF; 2: Only Indication
0: 3P4W
1: 3P3W
2: 2P3W
3: 1P2W
Version 1.0
Page 59 of 112