SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

7.1 CONTENTS AND SCOPES OF PARAMETERS

No.
Items
Mains
1
Mains AC System
2
Mains Normal Delay
Mains Abnormal
3
Delay
4
Mains Over Voltage
5
Mains Under Voltage
6
Mains Have Rules
Timers
1
Start Delay
2
Stop Delay
3
Pre-heat Delay
4
Cranking Time
5
Crank Rest Time
6
Safety On Time
7
Start Idle Time
8
Warming Up Time
9
Cooling Time
10
Stop Idle Time
11
ETS Solenoid Hold
12
Stop Duration
13
Louver Hold Open
HGM4020DC Genset Controller
HGM4020DC GENSET CONTROLLER USER MANUAL
Table 10 - Parameters Settings and Scope
Range
Default
(0-3)
0
(0-3600)s
10
(0-3600)s
5
(30-620)V
276
(30-620)V
184
(0-4)
0
(0-3600)s
1
(0-3600)s
1
(0-300)s
0
(3-60)s
8
(3-60)s
10
(1-60)s
10
(0-3600)s
0
(0-3600)s
10
(3-3600)s
10
(0-3600)s
0
(0-120)s
20
(0-120)s
0
(0-3600)s
30
Version 1.0
Description
0: 3 Phase, 4 Wire(3P4W);
1: 2 Phase, 3 Wire (2P3W);
2: 1 Phase, 2 Wire (1P2W);
3: 3 Phase, 3 Wire (3P3W).
The time from mains abnormal to normal or
from normal to abnormal;
When mains voltage has exceeded the set
value, Mains Over Voltage is active. When
set the value as 620V, the controller does
not detect over voltage signal. Backlash:
10V.
When mains voltage has fallen below the set
value, Mains Under Voltage is active. When
set the value as 30V, the controller does not
detect under voltage signal. Backlash: 10V.
0: A: Must have; B/C can't lack;
1:A: Must have; B/C can lack one;
2:A: Must have; B/C can lack two;
3:A: Can have; A/B/C can lack one;
4:A: Can have; A/B/C can lack two;
Time from auto start signal is active to
genset is started.
Time from auto start signal is deactivated to
genset is stopped.
Power-on time of heater plug before starter
is powered up.
Power-on time of starter for each time.
The waiting time before second power up
when engine start fails.
Alarms for low oil pressure, under speed,
under frequency/voltage, charge alt failure
are inactive.
Idle speed running time of genset at starting.
Warming time before genset takes load,
after it goes into high speed running.
Radiating time before genset stop, after it
unloads.
Idle speed running time at genset stopping.
Stop electromagnet's power on time at
genset stopping.
When "ETS time" is set as 0, it is time
needed between ending of genset idle delay
and genset complete stop;
When "ETS time" is not 0, it is time between
ending of ETS hold delay and genset
complete stop.
Keeping open time of Louver after genset's
complete stop;