Commissioning
2.2 STARTER commissioning tool
2.2.4

Activating online operation: STARTER via PROFINET IO

Online operation with PROFINET IO is implemented using TCP/IP.
Preconditions
● STARTER commissioning tool from version 4.1.5 or higher
● Control Unit CU320-2 PN
● Communication Board CBE 20 in the Control Unit
STARTER via PROFINET IO (example)
Figure 2-7
Procedure for activating online mode with PROFINET
1. Setting the IP address in Windows XP
2. Settings in the STARTER commissioning tool
3. Select online operation in the STARTER commissioning tool.
68
Connecting the programming device to the target device via PROFINET (example)
Assign the programming device (PG/PC) a fixed, free IP address. In our example, we
selected 169.254.11.1, based on the factory setting of the integrated Ethernet interface
X127 (169.254.11.22). Set the subnet mask to 255.255.0.0.
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2