Commissioning
2.2 STARTER commissioning tool
Restoring the factory settings
You can use this function to set all the parameters in the working memory of the Control Unit
to the factory settings. To ensure that the data on the memory card is also reset to the
factory settings, choose the "Copy from RAM to ROM" function. This function can only be
activated in the online mode. You activate the function by:
1. Call the shortcut menu "Drive unit > Target device > Restore factory settings".
2. Click on "OK" to acknowledge.
More information on how to use STARTER can be found in the SINAMICS S120 Getting
Started manual.
Operating support using wizards
Wizards are integrated in STARTER for various functions to support operation.
Create data records (offline) and copy
Drive and command data sets (DDS and CDS) can be added in the drive's configuration
screen. Click on the appropriate buttons to do this. Before data sets are copied, all the wiring
needed for both data sets should be completed.
For more information about data sets, refer to the Basics chapter in the SINAMICS S120
Function Manual Drive Functions.
Load project to target device.
You can use this function to load the actual project from the programming device into the
Control Unit. A consistency check is first made for the project. If inconsistencies are
detected, corresponding messages are output. You must resolve the inconsistencies before
loading. If the data are consistent, then they will be transferred into the work memory of the
Control Unit. In order to execute this function in the online mode, the following operator
actions are alternatively available:
1. Select the drive unit and call the menu "Project > Load to target system".
2. Select the drive unit and call the shortcut menu "Target device > Load to target device".
3. Select the drive unit and call the menu "Target system > Load > Load CPU/drive unit to
4. If the drive unit has a gray background, click on the symbol
56
In the following prompt window you can select as to whether you also wish to save the
factory setting in the ROM.
or
or
target device...".
or
target device...".
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2